Interactive Room Heat Load & Heat Transfer Simulator

Live Thermal Cutaway Diagram

ΔT = 13.0 °C
Solar: 650 W/m² Outdoor: 35.0 °C Roof Conduction: 720 W Walls: 890 W Solar Gain: 1,420 W Infiltration: 340 W AC COOLING Indoor: 22.0 °C Internal Load: 950 W
Solar Radiation (Window)
Wall Conduction
Roof Conduction
Internal (People/Lights/PC)
Air Infiltration

Live Heat Transfer Physics Equations

Q_cond = U × A × ΔT Conduction through walls & roof driven by U-value, surface area, and temperature difference.
Q_solar = A_win × SHGC × I_sun Solar heat transmitted through window glass based on Solar Heat Gain Coefficient & irradiance.
Q_int = Q_people + Q_lights + Q_equip Sensible + latent heat emitted by occupants, lighting fixtures, and electronics inside the room.
Q_inf = 1.21 × V_dot × ΔT Warm outdoor air leaking into the conditioned space through cracks and door openings.

Room & Climate Parameters

Outdoor Temp 35 °C
Indoor Setpoint 22 °C
Solar Irradiance 650 W/m²
Window Area 4.0 m²
Wall & Roof Insulation Medium
Glass Type (SHGC) 0.55
Occupants (People) 3 people
Lights & Equipment 450 W
Total Cooling Load
4,320 W
1.23 Tons of Refrig.
Dominant Heat Source
Solar Gain
33% of total load
Required Airflow
295 L/s
625 CFM (ΔT = 10K)
☀ Solar Window Gain 1,430 W (33%)
🧱 Exterior Walls Conduction 845 W (20%)
🏠 Roof Conduction (with Sol-Air) 715 W (17%)
💡 Internal Load (People + Equip) 840 W (19%)
💨 Air Infiltration 490 W (11%)